NOx Reduction Applications: Gas-Fired Boilers
Industrial boilers

For large industrial boilers, the CRI low-temperature Selective Catalytic Reduction (SCR) technology provides the ideal solution for NOx reduction, since the SCR can be installed in the stack at typical exhaust temperatures with no impact on the boiler or its operation.


Typical Boiler Application for the CRI SCR System:
 
Operating Temperature

 

Typical Application 325-450° F (163-232° C)

 

Range 325-700° F (163-371° C)
Pressure Drop

 

Typical Application

2-3 in. H2O (5-7.5 mbar)

 

Range As low as 1 in. H2O
Performance

 

NOx Conversion >90%

 

NH3 Slip 5-10 ppm or lower
Package boilers


For package boilers, CRI supplies a complete, ready-to-install SCR skid package. Standard packages are available for the complete range of firetube and watertube boilers.












Three standard skip packages

 

Boiler Horsepower Pounds/Hr. MmBTU/Hr.
Model A 100 to 500 3,450 to 17,250 4 to 20

Model B

500 to 1,000 17,250 to 34,500 20 to 42
Model C 1,000 to 2,000 34,500 to 69,000 42 to 85
Larger sizes can be custom designed to meet requirements